PGS-630A ncej mounted load break hloov yog siv rau kev rhuav tshem qhov ntsuas hluav taws xob 12/24/40.5kV, ntsuas tam sim no 630A, 50/60Hz lub zog xa hluav taws xob, kaw lub sijhawm tam sim no thiab tshaj qhov thauj khoom tam sim no ntawm lub zog hluav taws xob, nws tuaj yeem cais cov ntu ntu ntawm kev faib hluav taws xob uas ua txhaum tshwm sim. Qhov kev hloov pauv yog txuam nrog cov khoom siv hluav taws xob uas yog nrog cov thev naus laus zis tshiab. Cov kev hloov pauv muaj phau ntawv qhia, lub cev muaj zog, cov chaw taws teeb ua haujlwm hom. Lub tshuab hluav taws xob yuav raug ntsia rau hauv lub thawv stainless hlau, yog li nws tuaj yeem siv rau hauv ntau yam kev nyab xeeb. Tsis tas li ntawd, cov xaim / wireless modem tau nruab rau hauv lub thawv tswj tuaj yeem ua tiav cov chaw taws teeb saib xyuas thiab tswj. Nws yog ib qho yooj yim thiab yooj yim rau kev teeb tsa qhov hloov ntawm tus ncej, thiab qhov ntawd tuaj yeem txo tus nqi tua.
Ib puag ncig tej yam kev mob
♦ Cua kub:-40 ℃ ~ + 50 ℃;
♦ Cov av noo: 110%
♦ Qhov siab ≤3000m.
♦ Cua siab ≤700pa (sib npaug rau cua ceev 34m /s).
♦ Seismic siv: 8 degree.
♦ Qhov chaw teeb tsa: Tsis muaj hluav taws kub kub, kev phom sij tawg, tshuaj lom neeg corrosion thiab tsis tshua muaj kev vibration qhov chaw).
♦ Qib Pua Plag: Ⅲ chav kawm, Ⅳ chav kawm.
Ntaus cov lus piav qhia
MPP hom
♦ Porcelain bushing-molded cable qhov hluav taws xob
♦ Rubber split bushing-molded cable qhov hluav taws xob
♦ Integrative rubber bushing-wiring terminal outlet
♦ nrog surge arrestor
♦ Porcelain bushing-wiring terminal outlet
Technical Parameter
Yam khoom | PGS-12 | PGS-24 | PGS-40.5 |
Basic Rating | |||
Qhov siab tshaj qhov system voltage | 15 KV | 25.8 kV | 40.5KV |
Rated nruam tam sim no | 630a ua | 630a ua | 630a ua |
Rated zaus | 50/60Hz | 50/60Hz | 50/60Hz |
Lub sij hawm luv luv tiv taus tam sim no | 20 KA/4s | 25 KA/1s | 20 KA/1s |
Ua thiab tawg muaj peev xwm | |||
Feem ntau active load tam sim no | 630a ua | 630a ua | 630a ua |
Tus naj npawb ntawm kev ua haujlwm load-break | 400 x | 400 x | 400 x |
Short-circuit ua tam sim no (peak) | 50 KA | 50 KA | 50 KA |
Tus naj npawb ntawm kev ua haujlwm | 5x ua | 5x ua | 5x ua |
Cable charging tam sim no | 25 A | 25 A | 25 A |
Kab them tam sim no | 1.5 A | 1.5 A | 2 A |
Kaw lub voj voog tam sim no | 630a ua | 630a ua | 630a ua |
Rated tsis muaj-load transformer tawg tam sim no | 22 A | 22 A | 22 A |
Fais Fab Zaus Nrog Kev Ntsuas Tam Sim No | |||
10s (kev xeem ntub), theem-theem-lub ntiaj teb, hla kev sib cuag qhib | 4 5kv | 50 kV | 7 0kv |
1 min (kev sim qhuav), lub ntiaj teb, theem rau lub ntiaj teb | 50 kV | 60 kv | 95kv ua |
1 min (kev sim qhuav), hla kev sib cuag qhib | 50 kV | 60 kv | 110 KV TSI |
Impulse Withstand Current Test (1.2 x 50 µs) | |||
Phase-rau-theem, theem-rau-lub ntiaj teb | 85kv ua | 150 KV TSI | 195 kV ua |
Hla qhib kev sib cuag | 95kv ua | 150 KV TSI | 215 KV TSI |
Lwm Cov Kev Ntsuas & Specifications | |||
Internal arc xeem | 20kA / 0.1s | 20kA / 0.1s | 20kA / 0.1s |
Arc extinction nruab nrab | SF6Roj | SF6Roj | SF6Roj |
Rwb thaiv tsev nruab nrab | SF6Roj | SF6Roj | SF6Roj |
Creepage nrug (porcelain) | 550 hli | 8 40mm | 10 55mm |
Creepage nrug (silicon) | 6 10mm | 900 hli | 1250 hli |
IP qib | 54 | 54 | 54 |
Kev ua haujlwm zoo | |||
Lub sijhawm kaw / qhib | 1 sec | 1 sec | 1 sec |
Mechanical kev khiav hauj lwm (guaranteed) | 10000 zaug | 10000 zaug | 10000 zaug |
Kev khiav hauj lwm kub (* phau ntawv hom) | -25 (-40) ~ 70 ℃ | -25 (-40) ~ 70 ℃ | -25 (-40) ~ 70 ℃ |
Gas Siab | |||
Rated ua haujlwm siab (kg / cm2 G, ntawm 20 ° C) | 0.7 ua | 1.0 | 1.0 |
Cov khoom tawg-tiv thaiv kev ua haujlwm siab (kg / cm2 G) | 4 x6 | 4 x6 | 4 x6 |
Tsawg kawg ua haujlwm siab (kg / cm2 G) | 0.05 Nws | 0.0 | 0.0 |
Gas leakage tus nqi (cc / s) | ≤ 1% | ≤ 1% | ≤ 1% |
Zuag qhia tag nrho Dimensions
Qhov Loj (mm) | InstallationDimension (mm) | Packing loj (mm) | Kev ncua deb ntawm bushing (mm) | |||
A | B | C | Length × Dav | Length × Dav × siab | ||
10 KV | 225 | 435 ib | 500 | 500 × 390 hli | 1100 × 900 × 700 hli | 556 ib |
24 KV | 300 | 435 ib | 500 | 500 × 390 hli | 1300 × 1100 × 700 hli | 840 ua |
40.5KV | 350 | 435 ib | 500 | 700 × 390 hli | 1400 × 1200 × 700 hli | 1250 |