FZW32-24 hom sab nraum zoov high voltage cais lub tshuab nqus tsev so load hloov yog hom tshiab ntawm kev hloov pauv uas yog kev sib koom ua ke ntawm kev paub dhau los ntawm cov khoom siv hluav taws xob uas twb muaj lawm thiab kev tsim thev naus laus zis ntawm sab nraud. Qhov no load so hloov yog tsim los ntawm disconnector, nqus interrupter thiab kev khiav hauj lwm mechanism thiab lwm yam. Los ntawm kev siv lub hauv paus ntsiab lus ntawm lub tshuab nqus tsev cuam tshuam, nrog lub peev xwm arcing muaj zog, txhim khu kev qha, kev ua haujlwm ntev, ntim me me, tsis muaj kev phom sij tawg, tsis muaj kuab paug thiab lwm yam kom zoo dua. Cov khoom siv tuaj yeem siv rau hauv kev sib kis thiab kev xa tawm ntawm cov hluav taws xob hluav taws xob, metallurgy, mine, chemical kev lag luam thiab lwm lub tuam tsev ua cov cuab yeej tswj hwm, tshwj xeeb tshaj yog tsim nyog rau qhov chaw ua haujlwm nquag.

2. Hom lus piav qhia

hrt (2)

3. Cov xwm txheej ib puag ncig

ib. Qhov siab ≤1000m;

b. Ambient cua kub -30 ~ + 40 ℃;

c. Tus txheeb ze av noo: nruab nrab txhua hnub ≤95%, qhov nruab nrab txhua hli ≤90%;

d. Tsis tshua muaj kev vibration.

4. Technical Parameters

TSIS MUAJ.

Lub npe

Chav tsev

Tus nqi

1

Rated voltage

KV

nees nkaum plaub

2

Rated zaus

Hz

50

3

Rated tam sim no

A

1250

4

Rated active load breaking tam sim no

A

1250

5

Rated kaw voj breaking tam sim no

A

1250

6

5% rated active load breaking tam sim no

A

31.5 ib

7

Rated cable them tam sim no

A

10

8

Rated tawg peev xwm ntawm tsis muaj-load transformer

KVA

1600

9

Rated breaking capacitor bank tam sim no

A

100
 

10

1min fais fab zaus tiv taus voltage: lub tshuab nqus tsev vacuumfracture / theem-rau-theem, theem-rau lub ntiaj teb, cais tawg  

KV

 

50/65/79 ib

 

11

xob laim impulse withstand voltage: theem-rau-theem, theem-rau-lub ntiaj teb / cais tawg tawg  

KV

 

125/145 ib

12

Rated lub sij hawm luv luv tiv taus tam sim no (thermal stability)

LUB

25

13

Rated luv luv-circuit duration

S

4

14

Rated ncov tiv taus tam sim no (dynamic stability)

LUB

63

15

Rated luv-circuit kaw tam sim no

LUB

63

16

Neeg kho tshuab lub neej

Sijhawm

10000

17

Nqus interrupter hu rau yaig txwv

mm

0.5

18

Kev tuav tswj torque

Nm

≤200
  

 

 

 

 

 

19

  

 

 

 

Load break hloov lub tshuab nqus tsev interrupter assembling hloov

Clearance ntawm opencontacts  

mm

 10 ± 1
Nruab nrab qhib ceev

m/s

1.5 ± 0.2
Peb theem openasynchronism  

ms

 

Peb-theem kaw asynchronism  

ms

 

Kev ncua deb ntawm chargedbodies thiab theem-rau-lub ntiaj teb  

mm

 > 300
Auxiliary Circuit Court kuj

≥400

5. Kev teeb tsaTxoj kev,HloovDav thiab Phase-rau-theem Nyob deb

 

Installation txoj kev

 

Transverse dav

AB Phase-to-phase

nyob deb

BC theem-rau-theem

nyob deb

Kab rov tav / ntsug

12 25mm

500 hli

500 hli

6. Cov qauv tsim Kev kos duab

Lub load so hloov nrog peb-theem txuas, feem ntau muaj cov ncej, lub tshuab nqus tsev cuam tshuam, cov khoom siv hluav taws xob thiab lub caij nplooj ntoo hlav, lub tshuab nqus tsev thiab lub tshuab nqus tsev cuam tshuam tau tsau rau ntawm tus ncej ntawm insulator, lub caij nplooj ntoos hlav yog tsau rau ntawm tus ncej.